Sign In | Join Free | My hardware-wholesale.com
China Zhuhai Comking Electric Co.,Ltd. logo
Zhuhai Comking Electric Co.,Ltd.
Excellent Product, Best Service
Active Member

6 Years

Home > Outdoor Circuit Breaker >

Load Control Air Load Break Switch , High Voltage Load Break Switch Short Circuit Protection

Zhuhai Comking Electric Co.,Ltd.
Contact Now

Load Control Air Load Break Switch , High Voltage Load Break Switch Short Circuit Protection

Place of Origin : China

Brand Name : Comking

Certification : ISO9001,ISO14001,OHSAS18001

Model Number : CKWZ

Packaging Details : Wooden Packing

Delivery Time : 10-15 work days

MOQ : 1set

Price : To be discussed later

Payment Terms : L/C, T/T, Western Union

Rated Voltage : 12kV

Rated current : 630A

Rated frequency : 50Hz

Type : Outdoor

Contact Now

1. Description

CKWZ is a three-phase AC outdoor vacuum circuit breaker maximum up to 24kV rated voltage and 50Hz rated frequency.

2. Working Condition

2.1 Ambient air temperature: -45℃~+40℃,daily range of temperature: diurnal variation 25℃

2.2 Relative humidity: daily average data ≤95%, monthly average data ≤90%

2.3 Seismic capacity: ≤magnitude 8, horizontal acceleration ≤ 0.4g, vertical acceleration ≤ 0.2g

2.4 Altitude: ≤1000m

2.5 Pollution classification: IV.

2.6 Wind speed: ≤35m/s

2.7 Applicable in the places without fire, without explosion risk, and without violent vibration

(Exceeding above working condition is available as customized product)

3. Technical Data

Description Unit Parameter
Rated voltage kV 12 24
Rated frequency Hz 50 50
Rated current A 630 630
Rated short-time withstand current(4s) kA 20 20
Rated peak withstand current kA 50 50
Rated short-circuit making current(peak) kA 50 50
Rated short-circuit breaking current kA 20 20
Breaking times for rated short-circuit breaking current times 30 30
Mechanical life times 10000 10000
Power frequency withstand voltage(1min) kV 42/48 50/60
Lighting impulse withstand voltage kV 75/85 125/145
Clearance between open contacts mm 9±1 12±1
Withstand voltage for secondary circuit (1 min) V 2000 2000
Opening speed m/s 1.2±0.2 1.4±0.25
Closing speed m/s 0.8±0.2 0.8±0.2
Bounce time for contact’s closing ms ≤2 ≤2
Opening simultaneity for three-phase ms ≤2 ≤2
Loop resistance (without disconnector) μΩ <80 <80

4. Standard

---- GB1984-2003

---- GB/T11022-2011

---- GB/T11023-1989

---- GB311.1-1997

---- DL/T593-1996

---- DL/T402-1999

---- GB/T3309-1989

---- DL403-1999

---- IEC62271-100


Product Tags:

outside circuit breaker

      

3 phase breaker

      
China Load Control Air Load Break Switch , High Voltage Load Break Switch Short Circuit Protection wholesale